1.1 These requirements cover lined interior standpipe fire hose in the 1-1/2 and 2-1/2 inch sizes that is intended:
a) For fire-protection purposes only;
b) For use with inside standpipes installed in accordance with the Standard for the Installation of Standpipe and Hose Systems, NFPA 14;
c) For use on hose racks and reels and in cabinets where the specific combination of hose and rack, reel, or cabinet has been investigated and found acceptable;
d) To withstand infrequent service; and
e) To be periodically inspected and maintained while in service, as outlined in the Standard for the Care, Use, Inspection, Service Testing and Replacement of Fire Hose, Couplings, Nozzles and Fire Hose Appliances, NFPA 1962.
1.2 The 1-1/2 inch size hose is intended for use primarily by the building occupants for the control of incipient fires until the arrival of the fire department.
1.3 The 2-1/2 inch size hose is intended for use by fire departments and those trained in handling large water streams required during the more advance stages of fire on the inside of buildings or for exposure fire protection.
1.4 These requirements do not cover couplings nor their method of attachment.
This revision of ANSI/UL 219 dated January 30, 2024 includes an editorial change to Section 8.1.1, Twists of Hose Harmonization with UL 19.
RevisionsRed Line Std. (3)
CSDS Proposals (2)
CSDS Proposals
An electronic document associated with a UL Standard for Safety or Outline of Investigation, and issued by UL to propose:
UL LLC CRD (0)
Other Updates (0)
Referenced Standards (0)
Reverse Referenced Standards (1)
The cost to purchase this Standard varies depending on whether you are ordering a hardcopy, PDF or combination of the two. We also offer two different types of subscriptions: a one year and a three year.
You will be able to choose your purchase options on the following pages.
To serve you better, please update your account details.
Sample